Currently KSO – 190 Iva is even to the same equipment of the key world-famed producers and has the same price-quality relationship.

Quality management system guarantees that the whole manufacturing process corresponds to the procedures described in the quality manual. Each panel passes the acceptance trials.

Our quality management system satisfies the requirements of international standards series ISO 9001:2000 and includes:
  • Learning clients’ needs and products’ and services’ quality improvement regarding the customer requirements and the level of their satisfaction;
  • Strict quality control at any life circle stage of the products and cervices;
  • The process approach to managing the organization;
  • Arranging the favorable conditions for personnel motivation to provide high quality of goods and services. Advanced personnel training and development of its manufacturing and creative activity;
  • Implantation of advanced technologies including computer-aided manufacturing process facilities.

Our factory doesn’t do any harm to the environment and enables to save energy supply. Our products do not need any specific means of utilization when its product life is over.


KSO – 190 Iva



Range of application and function


KSO – 190 Iva is intended for switch-gears 6(10)kV voltage of three-phase alternating current with 50 Herz frequency in the circuits with isolated neutral terminal, earthed by arc-suppressing reactor or resistor.

KSO – 190 Iva is used for completing the modular, fitted and switch-gear devices of transformer substations.


Service conditions


Cubicles are the indoor electrical equipment;
  • Height above sea level – not more than 1000m;
  • Ambient air temperature – from 50 oС to + 40 oС;
  • Relative humidity not more than 80% at + 15 oС;
  • Ambient – non dangerously explosive, doesn’t contain current-conducting dust, aggressive gases and fumes of concentration wrecking materials and isolation;
  • Operating position – vertical; possible deflection from operating position 2 degrees in any direction;
  • KSO – 190 Iva operation should be executed in accordance with guideline.

KSO – 190 Iva

KSO – 190 Iva



Technical parameters KSO «Iva»


Table 1


Parameter Value
1 Rated voltage, кV 6; 10
2 Maximum operating voltage, кV 7,2; 12
3 Rated current, А
— main circuit
— collecting bus
— line breakers
— load-break switches
 
630; 1000; 1250
630; 1000; 1600
1000; 1250
630
4 Rated current of fuse filler, А 6,3; 10; 16; 20; 25;
31,5; 40; 50; 63; 80;
100; 125; 160; 200
5 Rated current of fuse disconnection, кА:
— rated current under 160 А
—rated current under 200 А
 
63
50
6 Rated current of current transformer, А 50; 75; 100; 150; 200;
300; 400; 600; 800;
1000
7 Short-time thermal current, кА/ 1 s 12,5; 20
8 Short-time electrodynamic current, кА 32; 51
9 Line breaker’s rated breaking current, кА 12,5; 20
10 Resistance to short circuit though currents of the load break isolators, кА:
— Rating initial value of the short-circuit current’s periodic componentа короткого замыкания
 
12,5; 20
11 Short-circuit making current of the load break isolators, кА 32; 51
12 Load break isolators’ rated breaking current in normal operating condition, А
— cable and air-line charging current
— cable and air-line charging current under monophase ground earth circuit
— transformer’s exciting current
 
25
50
25
13 Rated voltage of the auxiliary circuit, V:
— under constant-current
— under alternating current
— of the lighting circuit
 
100; 220
110; 220
36
14 Mechanical life (cycles В-tп-О):
— line breakers’
— load break isolators’ and disconnect switches’
— grounding switches’
 
50000
2000
500
15 Switching life (cycles В-tп-О):
— line breakers’, under breaking current 20 кА, at least
— load break isolators’, under breaking current 630 А (Сosφ=0,7), at least
 
100
100
16 Working life, years, at least 25
17 Protection degree GOST 14254 IP31
18 Operating temperature, oC -25:+40
19 Dimensions, мм:
— width
— depth
— height
 
300; 550; 750
1000
1950



Fuse fillers’ rated current for power transformer’s defense


Table 2


Urated, кV Overcharge Transformer rated capacity, кVА
40 63 100 160 250 400 630 1000 1250 1600
6 - 6 6 10 16 25 40 63 100 125 160
40% 6 10 16 20 32 50 80 125 160 -
10 - 6 6 6 10 16 25 40 63 80 100
40% 6 6 10 16 20 32 50 80 100 125



Symbol identification





Equipment fitted


  • Current transformers ТОЛ (ТЛК);
  • Zero-phase sequence current transformers ТДЗЛК, CSH;
  • Voltage transformer НАМИТ, ЗНОЛ, ЗНОЛП, НОЛ;
  • House transformer ТСКС-40;
  • Nonlinear overvoltage limiters;
  • Voltage detector with capacitance divider;
  • Protective relaying microprocessor units: «SEPAM 1000+» серий 20, 40, 80 — «Schneider Electric»; «IPR-A», «SMPR-1» — «ORION»; «Сириус-2» — «РАДИУС Автоматика»;
  • Fiber-optic arc defense «ОВОД-М» (by request);
  • Energy meters (by request);
  • Anti-condensate heaters (by request);
  • Uninterruptible power supply UPS (on-line) (involving line breaker).


Checklist


KSO – 190 Iva (according to questionnaire);
  • Spare parts and implements (according to order specification);
  • Bunched wires of interchamber connection ;
  • Operational documents: registration certificate, operating manual, registration certificate of the cell’s instruments and devices;
  • Single-line diagram of the switch-gear main circuits, electrical schematic diagram KSO – 190 Iva, secondary circuit layout chart, interchamber connection layout chart;
  • Bus bar bridge or jumper cable (on request).


KSO Iva Design


  1. Body is made of galvanized steel 2mm thick. Devices are connected by bearing heavy dynamic forces under short-circuit currents, transportation and mounting.
  2. Has three isolated compartments:


    KSO – 190 Iva

    Body face
    • Drive mechanism of the load break isolator and ground switch
    • Symbolic circuit of the chamber
    • Bezels
    • Doors’ intensified fixation
    • Voltage indication
  3. High-voltage and collecting bus compartments are divided for accident prevention. Conductor parts are isolated by automatic shutters. Such construction enables to perform operations in cell when collecting bus is alive.
  4. Access to collecting bus is provided through lift-off cover or low-voltage compartment.
  5. It is possible to lift-off the floor in order to mount and dress the cable.
  6. It is proved by testing that the door has a intensified construction enabling to localize the arc.
  7. Backwall has unloading valves activating by short circuit that provides safety to servicemen.
  8. Cell grounding terminal connected to outside grounding mat is made of cooper.


Switching equipment KSO-190 Iva
Circuit-breakers


Picture, Dimensions, WхHхD, мм Parameter Value
EVOLIS
Schneider Electric
Vacuum circuit-breaker
EVOLIS
KSO-190 Iva
550x535x429 мм

Rated voltage,кV
Max.working voltage, кV
Rated current, А
Rated breaking current, кА
Through current КЗ, кА
Time characteristic:
Contact breaking time, мс
Disconnection time, мс
Connection time, мс
Mechanical stability, number of operations
Switching stability, number of op-s (25 кА)

6/10
7,2/12
630/1250
25
62,5

<50
<60
<65
10000
100
BB/TEL
Tavrida Electric
Vacuum circuit-breaker
BB/TEL
KSO-190 Iva
540x474x256 мм

Rated voltage,кV
Max.working voltage, кV
Rated current, А
Rated breaking current, кА
Through current КЗ, кА
Time characteristic:
Contact breaking time, мс
Disconnection time, мс
Connection time, мс
Mechanical stability, number of operations
Switching stability, number of op-s (12,5/20 кА)

10
12
1000
12,5/20
32/51

<85
<95
<100
50000
100


KSO-190 Iva



Switch disconnector
ISARC





KSO-190 Iva
  1. Upper bell insulator
  2. Upper terminal
  3. Upper fixed contact
  4. Contact fingers
  5. Arcing contact rod
  6. Lower insulator
  7. Lower terminal
  8. Moving contact cylinder
  9. Guiding tulip contact
  10. Insulating connecting rod
  11. Operating shaft
  12. Cylindrical insulating element
  13. Earthing blades shaft
  14. Earthing blades
  15. Fixed contact
  16. Fixed piston
  17. Nozzle
  18. Moving arcing contact
  19. Rod
  20. Hinged shutter
  21. Field equalizing ring
  22. Shock aborber


On the steel frame are mounted bearing epoxy-resin isolators which fix contact elements.
The upper bell insulator (1) supports, on its outside, the main upper terminal (2) and, on its inside, the fixed contact (3), consisting of the contact fingers (4) and of the contact rod (5). With the switch disconnector in open position, the bell insulator is shut by a hinged shutter (20), actuated by the shaft (13) of earthing switch together with the blades of same, thus achieving a complete and reliable segregation of the live parts. This is the most prominent feature of the LBS series ISARC, covered by the patent n. 26743A-79 VEI.

The lower insulator (6) supports the lower terminal (7), the moving contact cylinder (8) and the guiding tulip contact assembly (9).


Activity description



KSO-190 Iva are equipped by three-pole double-throw load-break switch with earthing switch ISARC. The three poles of the load-break switch are mounted on a single galvanized steel frame and are operated by the single fitted spring drive using the potential energy of the cocked spring. The spring is cocked manually with the help of operating handle or by engine drive.
  • The design of the device provides mechanical overlapping by isolating shutters of the collecting bus compartment.
  • The open/close mechanical sequences are operated by:
    1. switch disconnector operating shaft;
    2. earthing switch shaft.

  • All necessary blockings are provided.
  • Operational type of the ISARC switches according GOST 17717-79-1Б &;#151; for frequent switching operations for rated currents before 630A.
  • Switches are integrally fused and have groundings.
  • Arc extinction is made in the air by compression.




Arc extinction description


  1. Cylinder of the moving contact
  2. Piston
  3. Nozzle
  4. Fixed cylinder












Load-break switch technical characteristics:

Parameter Value
Rated voltage Urated, кV 10
Rated current Irated, А 630
Short-time withstand current, кА: 12,5; 20;
Response speed, м/с on/off 5,8/2,8
Arc extinction time, мс 10-21
The number of rated load current commutations at cos φ=0,7 without revision, at least, cycles 100
Mechanical life, cycles 2000
Dimensions HхWхD, мм 940х390х894
Weight, kg 76



Relay protection, automatic machinery и electric energy registration in KSO-190 Iva.


Relay protection

Relay protection and automatic machinery microprocessor devices enable to realize:
  • All necessary types of connection protection 6(10) кV;
  • Measurable value identification;
  • Information storage;
  • Emergency parameters’ registration and storage;
  • Setting-up and protective relay settings’ changing via intranet;
  • involving microprocessor block of the relay protection to the SCADA-system;
  • Remote control of the switching unit by enterprise’s network.


For protection of different connections in KSO-190 Iva microprocessor units of relay protection and automatic machinery ORION, SEPAM are installed.


Telemechanics


On request switch-gear with KSO-190 Iva is completed with devices required for switch-gear connection to the telemechanics system that enables to realize such functions as:
  1. Telesignalization
  2. Telemetry
  3. Telecontrol

KSO-190 Iva



Leningradskaya oblast, Boksitogorsk.